find your coatings consultants
Find and contact a coatings consultant near you.

Series 264 | Elasto-Shield

Generic Type Modified Polyurethane
Common Usage Flexible liner providing a seamless monolithic membrane for use in potable water basins, steel tank floors and reservoirs. Also for areas requiring impermeability such as decorative ponds and secondary chemical containment.
Colors Black
Finish Gloss. Note: Prolonged exterior exposure will cause flattening of the finish.
Surfacer/Filler/Patcher Series 215, 217, 218, 265
Volume Solids 88.0 ± 2.0% (mixed)
Recommended DFT 50 to 80 dry mils (1270 to 2032 microns). Note: Multiple passes at timed intervals are required to achieve recommended dry film thickness. Timing is dependent upon material and substrate temperatures. See the Elasto-Shield Application Guide for additional instructions.
Curing Time
Temperature Recoat Window †† Full Cure Immersion
75°F (24°C) 3 hours at 50 mils DFT 24 hours Potable: 14 days †
Non-Potable: 48 hours
† Film thicknesses greater than 50 mils DFT will require additional time for solvent release. Curing time varies with air & substrate temperatures, air movement, humidity and film thickness. †† Note: Scarify the surface and apply a coat of Series V260 Tneme-Bond before recoating if the maximum recoat time has been exceeded.
Volatile Organic Compounds 0.75 lbs/gallon (90 grams/litre)
Theoretical Coverage 1,396 mil sq ft/gal (34.2 m²/L at 25 microns).
Number of Components Two—Liquids: Part A (resin)) and Part B (iso)
1
Category
2
Chemical Name(required)
3
Concentration
4
What is this?

Note: Not Recommended (NR), Not Tested (NT), Please Call (PC)

 

Chemical Recommended Use - What is this?

The chemical resistance data listed on this website should only be used for general reference purposes. Substrates, temperatures, chemical combinations, and other variables can affect the performance of a coating in chemical exposure. Please contact your local to finalize the most appropriate system for your project.

Click the following button to download a PDF of the list of chemicals below.

1 Product is NOT suitable for direct or indirect food contact. Intended Use and temperature information relates    to product's performance capabilities only.

2 Product is suitable for direct or indirect food contact. Reference the product data sheet for more information.


Recommended Use
Chemical Occasional Contact Frequent Contact Secondary Containment Cargo Immersion Immersion Service

1 Product is NOT suitable for direct or indirect food contact. Intended Use and temperature information relates    to product's performance capabilities only.

2 Product is suitable for direct or indirect food contact. Reference the product data sheet for more information.

  • Color cards, swatches and fan decks are offered at no charge, by request , for more accurate color selection. Expert custom color matching is also available by contacting your Tnemec Coatings Consultant .
  • Deeptone colors may be more expensive than lighter colors. Please contact your Tnemec Coatings Consultant to verify product/color availability and pricing.
These digital colors should not be used to finalize your color selection. Please read our disclaimer . Use the color swatch tool on the left to request official color swatches.

Color Swatch Packet

Request another

(maximum 6 color swatches)

You haven't added any color swatches to your packet. Select some colors now by clicking a color above and then clicking the 'Request a Swatch' button on the color.

The products listed below are not exact equivalents. They are only products that you may consider as alternatives in a general sense. Substrate type, condition, temperatures, surface preparation, primer/topcoat selection and intended use are just a few factors that will affect product selection. Please contact your local Tnemec Coatings Consultant for product recommendations.

This ProductModified Polyurethane
Volume Solids Rec. DFT V.O.C. # of Components
88.0 ± 2.0% (mixed) 50 to 80 dry mils (1270 to 2032 microns). Note: Multiple passes at timed intervals are required to achieve recommended dry film thickness. Timing is dependent upon material and substrate temperatures. See the Elasto-Shield Application Guide for additional instructions. 0.75 lbs/gallon (90 grams/litre) Two—Liquids: Part A (resin)) and Part B (iso)
Series 406 | Elasto-Shield Aromatic Polyurethane Hybrid
Hide this product's data
Volume Solids Rec. DFT V.O.C. # of Components
100% (mixed) † 25.0 to 125.0 mils (635 to 3175 microns). Maximum of 75 mils DFT for applications in potable water. EPA Method 24: 0 lbs/gallon (0 grams/litre) † Two: Part A (iso) and Part B (resin)